    Abstract : This paper analyzes the harmonic source, harmonic characteristics and hazards of the power grid, and compares the situation before and after the input of the active power filter through the application of the active filter in the low voltage distribution system of a large steel company . It shows that the harmonic filter technology of active power filter is one of the effective means to improve the power quality of the power supply. The generated harmonics can be controlled within the minimum range to achieve scientific and rational use of electricity, inhibit grid pollution, improve power quality, and ensure electrical quality. The role of equipment security.

    Keywords : power quality; harmonics; active filtering

    1 Power Quality and Harmonics

    1.1 Harmonic Generation

    With the increasing application of power electronic converter devices, electrical energy has been more fully utilized. However, the wide application of non-linear power devices has produced a large number of distorted current harmonics. The flow of distorted currents in the power grid has caused harmonic voltages; harmonic pollution has increasingly threatened the safety, stability, and economic operation of power systems. This has a great impact on the linear load and other users of the same network. Harmonics have been accompanied by electromagnetic interference and power factor reduction and are classified as the three major hazards of the power system. Therefore, it is of great significance to understand the principle of harmonic generation and to study the elimination of high-order harmonics in power supply and distribution systems to improve the quality of power supply and ensure the safe and economical operation of power systems. Harmonic measurement is an important branch of harmonics and plays an important role in suppressing harmonics and solving harmonic generation problems. Therefore, the measurement and analysis of harmonics is an important task in power system analysis and control, and it is an important prerequisite for relay protection and fault measurement.

    The main harmonic generation sources are as follows:

    Name

    Industry

    Frequency conversion device

    Commercial, municipal, civil, public utilities, industrial and mining companies, etc.

    UPS, switching power supply, inverter power supply

    Utilities, business, electronics, communications, etc.

    Subway, light rail, charging station (pile)

    traffic

    Single (multi)crystalline silicon production equipment, intermediate frequency furnace

    manufacturing

    Arc Furnace, AC Arc Welding Machine, Induction Heating Device

    Machinery, Energy, Chemicals

    1.2 Harmonic Harm

    1.2.1 Increase the additional loss of power components and cause fires.

    Harmonics cause additional losses in the components of the utility grid, reducing the efficiency of power generation, transmission, and electrical equipment. A large number of third harmonics passing through the midline will overheat the line and even cause a fire.

    1.2.2 Impact on the normal operation of electrical equipment.

    Harmonics will affect the normal operation of electrical equipment and cause electrical machinery to produce mechanical vibrations and noises, which will cause severe overheating of the transformer and cause overheating of capacitors, cables, etc., insulation aging, and shortened life span, resulting in damage.

    1.2.3 Causes grid resonance.

    This kind of resonance may amplify the harmonic current several times or even dozens of times. It will pose a great threat to the system, especially to the capacitor and the reactor connected in series with it. The capacitor and the reactor are often burned.

    1.2.4 The relay protection malfunctions and the electrical measurement error is too large.

    Harmonics will lead to relay protection, especially the malfunction of microcomputer integrated protection devices and automatic devices, resulting in unnecessary power supply interruptions and production losses; harmonics will also cause inaccurate metering of electrical measuring instruments, measurement errors, and power management Department or power users bring economic losses.

    1.2.5 Crash the industrial control system.

    Harmonic sources or higher harmonics in the vicinity may interfere with communication and information processing equipment, and noise may occur at a low level, which may degrade communication quality. The computer may not be able to work properly. If it is heavy, then the information will be lost and the industrial control system will crash.

    1.3 National standards for harmonic treatment

    GB/T14549-1993 "Power Quality: Harmonics in the Utility Grid"

    GB/T15543-2008 "Power quality: three-phase voltage allow unbalance"

    GB/T12325-2008 Power Quality: Allowable Variation of Supply Voltage

    GB/T12326-2008 "Power Quality: Voltage Fluctuations and Flicker Changes"

    GB/T18481-2001 "Power Quality: Temporary Overvoltage and Transient Overvoltage"

    GB/T15945-2008 Power Quality: Allowable Frequency Deviation of Power System

    GB7625.1-1998 Harmonic current limits issued by low-voltage electrical and electronic products

    GB/T15576-1995 "General technical conditions for low-voltage reactive power static compensation device"

    2 Typical Application Scenarios

    2.1 Project Background

    An iron and steel company is an extremely large iron and steel conglomerate that integrates coking, sintering, smelting, rolling and scientific research and development. Its X rolling mills mainly produce steel products such as plate, due to production needs, in the low-voltage distribution system. The equipment on the secondary side of the transformer is mainly a motor, and the inverter drives the motor. Because the internal structure of the frequency converter uses a large number of non-linear elements, a large number of harmonics are generated in the working process.

    There is a certain impact load on the plate during the rolling process, and the production process is not continuous. This causes the operating voltage/current to fluctuate and discontinuous, and the change of the operating current also causes the harmonic current to fluctuate.

    Real-time monitoring of current and voltage fluctuations

    2.2 Project Plan

    Our company has developed a corresponding solution for the harmonics of the power grid of No. 2 cooling bed in the rolling mill of the company. The self-developed shunt active power filter ( ANAPF ) is used to perform centralized control on the outgoing side of the transformer. The filter can automatically track the harmonic current generated by the load and effectively filter out harmonics, thus ensuring the safe and reliable operation of the entire system.

    System governance shows as follows:

    2.3 Project Effect

    After the active power filter is put into operation , harmonic voltage and harmonic current control effects are:

    Pre-treatment voltage and current waveforms

    Voltage and current waveforms after treatment

    Current distortion rate before treatment

    Current distortion rate after treatment

    After the active power filter was put into operation, the total current distortion rate decreased from 82.1% to 4.4%, the current distortion rate of the fifth harmonic dropped from 67.0% to 1.9%, and the current distortion rate of the seventh harmonic dropped from 43.8%. 2.0%. The quality of the power grid has been significantly improved, and it has been applied to rapidly changing loads, which has significantly suppressed the harmonics generated by non-linear loads of the power supply system during operation, and fundamentally improved the power quality of the entire power supply system. , effective protection of the normal operation of the production line equipment.

    3 Introduction to ANAPF Active Filters

    3.1 Active Filter Main Specifications

    Wiring

    Three-phase three-wire or three-phase four-wire

    Access voltage

    3×380V ±10%

    Access frequency

    50Hz ±2%

    Dynamic compensation response time

    Dynamic response <4ms, full response time <20ms;

    On-off level

    10kHz

    Function settings

    Only harmonics are compensated, only reactive power is compensated, both harmonics are compensated and reactive power is compensated; manual and automatic switching are performed.

    Harmonic compensation times

    2-21 times

    Type of protection

    DC over-voltage IGBT over-current device temperature protection

    Overload protection

    Automatic current limit in the set value, no overload occurs

    cooling method

    Smart air cooling

    noise

    < 65db (in the cabinet and operating in the rated state)

    Working temperature

    -10°C to +45°C

    Working environment humidity

    <85%RH non-condensing

    Installation occasion

    Indoor installation

    Altitude

    ≤1000m (for use at higher altitudes)

    Incoming and outgoing ways

    Down in and out

    Protection level

    IP21

    Intelligent communication interface

    RS485/MODBUS-RTU

    Remote monitoring

    Optional

    Overall size (mm)

    (W×D×H)

    30A

    50A

    75A

    100A

    600×500×1500

    600×500×1500

    600×500×1800

    800×600×2200

    Weight (kg)

    Three-phase four-wire

    Three-phase three-wire

    30A, 50A

    75A, 100A

    30A, 50A

    75A, 100A

    280

    360

    240

    290

    3.2 Active Filter Quotation and Component List

    Model Number: ANAPF100-400/B

    Reference price: 120,000 yuan/set

    The main product details:

    No.

    Name

    Model number

    Quantity

    1

    APF electrical cabinet

    800X600X2200

    1

    2

    Converter

    APFCOV-CVT100

    1

    3

    Controller

    APFMC-C100

    1

    4

    Reactor

    APF-RE.(S)DG-100

    1

    5

    Active current transformer

    LT208-S7

    3

    6

    filter

    DL-1TH1

    2

    7

    breaker

    CVS160FTM160D4P3D

    1

    8

    Contactor

    LC1D150M7C

    1

    9

    MCB

    NDM1-63C32

    1

    10

    Intermediate relay

    MY4NAC

    2

    11

    R type transformer

    R320-0.38/0.22

    1

    12

    Harmonic Detector

    ACR350EGH

    1

    13

    wire

    16mm2

    Some

    14

    wire

    4mm2

    Some

    4 Conclusion

    The active filter device introduced in this paper adopts a modular design and has a very fast response time. One machine can be multi-energy, it can not only make up for harmonics, but also can make up for reactive power; the advanced main circuit topology and control algorithm are more accurate. More stable operation; easy to use, easy to operate and maintain. The active filter device saves the user's investment cost, shortens the construction period, and provides an efficient compensation device for the harmonic treatment project of the low-voltage distribution network, which has good application value and application prospects.

    【references】

    [1] GB/T 14549-1993 "Power Quality: Harmonics in Public Grids"

    [2] Ankerui Electric Co., Ltd. Product Manual. 2013.01.

    [3] Wu Jingchang. Power system harmonics, Beijing: China Power Science and Technology Press, 1998

    About the Author:

    Xu Shuang, female, undergraduate, Ankerui Electric Co., Ltd., the main research direction for the smart grid power distribution, Email: Mobile QQ

    "AAPF Active Power Filter Device Design and Application Atlas" (atlas number: ACR13CDX701) is edited by Ankerui Electric Co., Ltd. This atlas combines the characteristics of ANAPF active power filter device products, based on electrical design specifications, research Eliminating the problem of high-order harmonics in the power supply and distribution system to achieve the goal of improving the quality of power supply and ensuring the safe operation of the power system. The Atlas is applicable to the design and modification of harmonic suppression and comprehensive management of electrical equipment in industrial, civil, and public buildings in new construction, reconstruction, expansion, and technological transformation projects. If you need atlas, please provide your organization's name, department, address, zip code, contact person, contact telephone number, email address, fax 021-69155331, mail or QQ to Ankeru Xu cream engineer, Ankerui Electric will give you a free gift. .

    Touch Free Car Wash Equipment

    Leisuwash specializing in manufacture Automatic Car Wash Machine, Touchless Car Wash , Automatic Touchless Car Wash, touchless car wash equipment, robot car wash, smart car wash system, leisuwash 360, leisuwash leibao 360, laserwash 360, leisuwash touchless car wash machine, leisu wash touchless car wash automatic, leisu wash 360 high pressure touchless car wash equipment, robo car wash, touch free car wash, leisuwash 360 touch free car wash, leisuwash 360 price, automatic car wash price, leisuwash in malaysia, no touch automatic car wash machine.
    Leisuwash 360 touchless car wash machine high intelligent high quality, with car wash + car care + drying process totally, each car wash takes time 1 minute to 5 minutes which depends on the car wash mode.
    Automatic touch free car wash equipment more and more popular in car wash business market, as can save employee fees and wash time mostly, bring investor much more benefit profit return. That's why choose the automatic car washing system.

    Touch Free Car Wash Equipment,Automatic Car Wash,Leisuwash Touchless Car Wash,Automatic Car Wash Machine

    Hangzhou Leisu Cleaning Equipment Co.,Ltd , https://www.sdlaserwash.com

    Previous Post: New Process Technology of Low Grade Zinc Oxide Hydrometallurgy
    Next Post: Application of beneficiation equipment in barite beneficiation
    Home
    Recent Posts
    • Google Music will release the iOS platform App C…
    • Low cost, high strength, China's successful …
    • Study on Preparation of Feed Grade Defluorinated…
    • Sand and tin mine general industrial indicators …
    • New Process Technology of Low Grade Zinc Oxide H…
    • User-side power grid harmonic harm and active fi…
    • Application of beneficiation equipment in barite…
    • Sulphur mine mining development program
    • Lead and zinc tailings utilization examples
    • Measurement of waste non-ferrous metal resources
    • Research progress on molybdenum ore beneficiatio…
    • Classification of materials
    • New technology and new technology of jigging ben…
    • Cixi bearing foreign anti-dumping differential
    • What are the purposes and tasks of production ex…
    • Production example of cation reverse flotation o…
    • Use of rare earth element bismuth (Tb)
    • Warg custom wardrobe, teach you to distinguish p…
    • Application of atomization roasting in the prepa…
    • Grinding equipment and applications (8)